Vennligst vent...
Produktet ble lagt i handlekurven. Se handlekurven her

APC SMART-UPS RT 3000VA 120V

Forsiden UPS & Power Batteries APC SMART-UPS RT 3000VA 120V
Du må logge inn for å handle/se priser.
APC SMART-UPS RT 3000VA 120V (SURTA3000XL)

APC SMART-UPS RT 3000VA 120V

Varenr.:
SURTA3000XL
EAN:
0731304231479
  • Kapasitet 3kVA
Beskrivelse

APC SMART-UPS RT 3000VA 120V


APC Smart-UPS RT, 3000VA/2100W, Input 120V/Output 120V, Interface Port DB-9 RS-232, Smart-Slot, Extended runtime model, Rack Height 3 U

Includes: CD with software, Smart UPS signalling RS-232 cable, User Manual

Product Overview

Smart-UPS RT Features

Availability

Automatic internal bypass Supplies utility power to the connected loads in the event of a UPS overload condition or fault.
Scalable runtime Allows additional run time to be quickly added as needed.
Intelligent battery management Maximizes battery performance, life, and reliability through intelligent, precision charging.
Hot-swappable batteries Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Automatic restart of loads after UPS shutdown Automatically starts up the connected equipment upon the return of utility power.
Temperature-compensated battery charging Prolongs battery life by regulating the charge voltage according to battery temperature.

Manageability

Network manageable Monitor and control the UPS and access environmental information remotely via included PowerChute software or APC's Network Management Card with temperature monitoring (included in all models above 3kVA).
InfraStruXure Manager compatible Enables centralized management via APC's InfraStruXure Manager.
SmartSlot Customize UPS capabilities with management cards.
LED status indicators Enables quick understanding and response to visual indicators showing UPS status.
Serial Connectivity Provides management of the UPS via a serial port.

Adaptability

Plug-and-Play external batteries Ensures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
Rack/Tower convertible Protects the initial investment in the UPS when migrating from tower to rack-mount environment.
Flash-upgradeable firmware Easy implementation of new firmware upgrades.

Serviceability

User-replaceable batteries Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
Automatic self-test Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Predictive failure notification Provides early-warning fault analysis ensuring proactive component replacement.
Disconnected battery notification Warns when a battery is not available to provide backup power.
Audible alarms Actively let you know if the unit is on battery, if the battery is low or if there is an overload condition.

Protection

Frequency and voltage regulation Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Power conditioning Protects connected loads from surges, spikes, lightning, and other power disturbances.
Input power factor correction Minimizes installation costs by enabling the use of smaller generators and cabling.
Generator compatible Ensures clean, uninterrupted power to the loads in the event of an extended power outage
Cold-start capable Provides temporary battery power when the utility power is out.
Resettable circuit breakers Enables quick recovery from UPS overload events.
Safety-agency approved Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment. UL, FCC, CE, C-Tick approvals.
Technical Specifications

Output

Output Power Capacity 2100 Watts / 3000 VA
Max Configurable Power 2100 Watts / 3000 VA
Nominal Output Voltage 120V
Output Voltage Distortion Less than 3%
Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Crest Factor 3 : 1
Waveform Type Sine wave
Output Connections
(6) NEMA 5-15R
(2) NEMA 5-20R

Input

Bypass Internal Bypass (Automatic and Manual)
Nominal Input Voltage 120V
Input Frequency 50/60 Hz +/- 5 Hz (auto sensing)
Input Connections
NEMA L5-30P
Cord Length 10 feet ( 3.05 meters)
Input voltage range for main operations 90 - 150V

Batteries & Runtime

Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Included Battery Modules 2
Typical recharge time 2.50 hour(s)
Replacement battery cartridge RBC44
RBC™ Quantity 1
Typical Backup Time
at Half Load
33.9 minutes (1050 Watts)
Typical Backup Time
at Full Load
14.1 minutes (2100 Watts)
Runtime Chart Smart-UPS RT
Extended Run Options APC SMART-UPS RT 3000VA 120V

Communications & Management

Interface Port(s) DB-9 RS-232,Smart-Slot
Available SmartSlot™ Interface Quantity 1
Control panel LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators
Audible Alarm Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm
Emergency Power Off (EPO) Yes

Surge Protection and Filtering

Surge energy rating 480 Joules
Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449

Physical

Maximum Height 17.00 inches (432 mm)
Maximum Width 5.10 inches (130 mm)
Maximum depth 26.00 inches (660 mm)
Rack Height 3U
Net Weight 120.00 lbs. ( 54.55 kg)
Shipping Weight 140.00 lbs. ( 63.64 kg)
Shipping Height 13.68 inches (347 mm)
Shipping Width 23.73 inches (603 mm)
Shipping Depth 38.60 inches (980 mm)
Color Black
Units per Pallet 6.00

Environmental

Operating Environment 32 - 104 °F (0 - 40 °C)
Operating Relative Humidity 0 - 95%
Operating Elevation 0-10000 feet (0-3000 meters)
Storage Temperature 5 - 113 °F (-15 - 45 °C)
Storage Relative Humidity 0 - 95%
Storage Elevation 0-50000 feet (0-15000 meters)
Audible noise at 1 meter from surface of unit 55 dBA
Online Thermal Dissipation 655 BTU/hr

Conformance

Regulatory Approvals CSA,FCC Part 15 Class A,UL 1778
Standard Warranty 2 years repair or replace
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.

Selv om vi gjør vårt beste for å gi relevant informasjon, så er bildene kun for å gi et generelt inntrykk, og selve varen er ikke nødvendigvis akkurat slik som avbildet. Dersom det er forskjeller mellom produktoverskrift, beskrivelse og bilde, så er det produktoverskriften som gjelder (f.eks. PCer kommer ikke nødvendigvis med skjerm selv om bildet viser det). Hvis noe er uklart, vennligst send epost til kundestøtte før du bestiller. Vi tar forbehold om trykkfeil og endring av priser og spesifikasjoner uten varsel.